Work Space Minimum Clear Distances


Voltage to Ground Condition 1 Condition 2 Condition 3
0 to 150 Volts 3 feet 3 feet 3 feet
151 to 600 Volts 3 feet 3-1/2 feet 4 feet

Where:

  • Condition 1 is for electrical equipment mounted or set on a wall where the wall on the opposing side of the room is insulated.
  • Condition 2 is for electrical equipment that is mounted on a wall and the wall on the opposing side of the room is grounded.
  • Condition 3 is for electrical equipment is mounted or set on a wall and other electrical equipment is mounted on an opposing wall.