Flanged Lateral - AWWA C110, DI (in)
- Flanged lateral fittings are not included in AWWA C110/A21.10
- For flange dimensions see Flange - ANSI Class 125, C110, DI
- AWWA C110/A21.10 - Ductile-Iron and Gray-Iron Fittings (3" to 48")
- AWWA C104/A21.4 - Standard for Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for Water
- ASME B16.1 - Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250 (Flange surfaces shall be faced and drilled in accordance with ANSI Class 125)
- All ductile iron flanged fittings shall be rated for water pressure of 250 PSI.
- Flanged ductile iron fittings in 24 inch and smaller sizes may be rated for 350 psi with the use of special gaskets.
Pipe Size | F | G | Approx. Weight (lb) | |
---|---|---|---|---|
Run | Branch | |||
3 | 3 | 10 | 3 | 50 |
4 | 3 | 12 | 3 | 70 |
4 | 4 | 12 | 3 | 75 |
6 | 4 | 14 1/2 | 3 1/2 | 105 |
6 | 6 | 14 1/2 | 3 1/2 | 130 |
8 | 4 | 17 1/2 | 4 1/2 | 153 |
8 | 6 | 17 1/2 | 4 1/2 | 190 |
8 | 8 | 17 1/2 | 4 1/2 | 200 |
10 | 4 | 20 1/2 | 5 | 230 |
10 | 6 | 20 1/2 | 5 | 290 |
10 | 8 | 20 1/2 | 5 | 335 |
10 | 10 | 20 1/2 | 5 | 300 |
12 | 4 | 24 1/2 | 5 1/2 | 355 |
12 | 6 | 24 1/2 | 5 1/2 | 370 |
12 | 8 | 24 1/2 | 5 1/2 | 395 |
12 | 10 | 24 1/2 | 5 1/2 | 420 |
12 | 12 | 24 1/2 | 5 1/2 | 460 |
14 | 6 | 27 | 6 | 500 |
14 | 8 | 27 | 6 | 525 |
14 | 10 | 27 | 6 | 555 |
14 | 12 | 27 | 6 | 600 |
14 | 14 | 27 | 6 | 640 |
Pipe Size | F | G | Approx. Weight (lb) | |
---|---|---|---|---|
Run | Branch | |||
16 | 6 | 30 | 6 1/2 | 655 |
16 | 8 | 30 | 6 1/2 | 680 |
16 | 10 | 30 | 6 1/2 | 715 |
16 | 12 | 30 | 6 1/2 | 755 |
16 | 14 | 30 | 6 1/2 | 800 |
16 | 16 | 30 | 6 1/2 | 850 |
18 | 8 | 32 | 7 | 820 |
18 | 10 | 32 | 7 | 855 |
18 | 12 | 32 | 7 | 1005 |
18 | 14 | 32 | 7 | 940 |
18 | 16 | 32 | 7 | 990 |
18 | 18 | 32 | 7 | 1035 |
20 | 10 | 35 | 8 | 1095 |
20 | 12 | 35 | 8 | 1130 |
20 | 14 | 35 | 8 | 1170 |
20 | 16 | 35 | 8 | 1220 |
20 | 20 | 35 | 8 | 1345 |
24 | 24 | 40 1/2 | 9 | 2020 |
36 | 36 | 60 | 19 1/2 | 5740 |