Superheat Correction Factor

on . Posted in Tables

Tags: Heat Tables

The table below is used to calculate the superheat correction factor, Ksh when sizing a relief valve in steam service:

Set PressureTemperature (degrees Fahrenheit)
40 1.00 0.99 0.93 0.88 0.84 0.81 0.77 0.74 0.72 0.70
60 1.00 0.99 0.93 0.8S 0.84 0.S1 0.77 0.75 0.72 0.70
80 1.00 0.99 0.93 O.S8 0.84 0.81 0.77 0.75 0.72 0.70
100 1.00 0.99 0.94 0.89 0.84 0.81 0.77 0.75 0.72 0.70
120 1.00 0.99 0.94 0.89 0.84 0.81 0.78 0.75 0.72 0.70
140 1.00 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.70
160 1.00 0.99 0.94 0.89 0.S5 0.81 0.78 0.75 0.72 0.70
180 1.00 0.99 0.94 0.89 0.85 0.81 0.78 0.75 0.72 0.70
200 1.00 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.70
220 1.00 0.99 0.95 0.89 0.85 0.81 0.78 0.75 0.72 0.70
240 - 1.00 0.95 0.90 0.85 0.81 0.78 0.75 0.72 0.70
260 - 1.00 0.95 0.90 0.85 0.81 0.78 0.75 0.72 0.70
280 - 1.00 0.96 0.90 0.85 0.81 0.7S 0.75 0.72 0.70
500 - 1.00 0.96 0.90 0.85 0.81 0.78 0.75 0.72 0.70
550 - 1.00 0.96 0.90 0.86 0.82 0.78 0.75 0.72 0.70
400 - 1.00 0.96 0.91 0.86 0.82 0.7S 0.75 0.72 0.70
500 - 1.00 0.96 0.92 0.86 0.82 0.78 0.75 0.73 0.70
600 - 1.00 0.97 0.92 0.87 0.82 0.79 0.75 0.73 0.70
800 - - 1.00 0.95 0.8S 0.83 0.79 0.76 0.73 0.70
1000 - - 1.00 0.96 0.89 0.84 0.78 0.76 73.00 0.71
1250 - - 1.00 0.97 0.91 0.85 0.80 0.77 0.74 0.71
1500 - - - 1.00 0.93 0.86 0.81 0.77 .0.74 0.71
1750 - - - 1.00 0.94 0.86 0.81 0.77 0.73 0.70
2000 - - - 1.00 0.95 0.86 0.80 0.76 0.72 0.69
2500 - - - 1.00 0.95 0.85 0.78 0.73 0.69 0.66
3000 - - - - 1.00 0.82 0.74 0.69 0.65 0.62

 